How does winding resistance tester differ from secondary injection testing?

 The main differences between a winding resistance tester and secondary injection testing are:


Purpose:

Winding resistance tester: Measures the resistance of the windings in a transformer, circuit breaker, or other electrical equipment to assess their condition and identify potential issues.

Secondary injection testing: Evaluates the performance and operation of protective relays, trip circuits, and associated secondary circuits in electrical systems.

Test Currents:

Winding resistance tester: Applies a low-level DC current (typically less than 10A) to the windings and measures the voltage drop to calculate the resistance.

Secondary injection testing: Injects a simulated secondary current into the protective relay or trip circuit to verify its operation and response.

Test Connections:

Winding resistance tester: Directly connects to the equipment's terminals or windings to measure the resistance.

Secondary injection testing: Connects to the secondary circuits of the equipment, such as current transformer (CT) or potential transformer (PT) circuits.

Scope of Testing:

Winding resistance tester: Focused on assessing the physical condition and integrity of the windings themselves.

Secondary injection testing: Evaluates the overall functionality and performance of the protective relay, trip circuit, and associated secondary equipment.

Measurement Parameters:

Winding resistance tester: Primarily measures the resistance value of the windings.

Secondary injection testing: Measures the relay's operation time, pickup and dropout values, and other performance characteristics.

Equipment Type:

Winding resistance tester: Specialized instrument designed for measuring winding resistances.

Secondary injection testing: Typically uses a secondary injection test set or relay test set.

In summary, winding resistance testing is used to assess the condition of the primary windings, while secondary injection testing is used to evaluate the performance and functionality of the secondary circuits and protective relays. Both tests serve different but complementary purposes in the overall maintenance and testing of electrical equipment.